DZ47LE-63 Residual Current Operated Circuit Breaker

Print current page

Product Description

  • brief introduction
  • technical parameter
  • Product size

Application

The DZ47LE residual current operated  circuit breaker is applicable to the circuit with an alternating current of 50Hz, rated-voltage single pole and two lines/two poles 230V, three poles/three poles and four lines/four poles 400V, and a rated current up to 63A; when the human body gets an electric shock or thenetworkleakcurrent exceeds the specified value, the residual current operated  circuit breaker can rapidly cut off the power supply in trouble within a very short time for the safety of the human body and the powered equipment. With the function of overload and short circuit protection,  the residual current operated  circuit breaker can be used to protect the circuit or motor from being damaged by overload and short circuit, and can also be used for not–frequent operational transformation in the circuit under normal condition.The product meets the standards of IEC 61009-1.

Normal operating conditions

1. air temperature: -5°C~+40°C, the mean value is no higher than +35°C within 24 hours .

2.Altitude: not higher than 2000m in installation site.

3. Atmospheric conditions:The air Relative humidity in the installation point will can't more than 50% in the highest temperature 40 C

The air Relative humidity can't more than 90%, in the month most humidity and Monthly average minimum temperature not higher than 25 C.

4.Installation category: II, III grade.

5.Pollution degree: 2 grade.

6.Installation: Standard rail installation TH35-7.5 DIN rail

7. Installation conditions: Installation place of the external magnetic field in any direction should not exceed 5 times of the geomagnetic field, leakage

circuit breaker shall be installed vertically, generally handle up to position, turning on the power supply installation area should be no significant impact

and vibration.

8.Connection: screw wiring.


Ordering information

Please remark these points when place the order.

A. Model .Name; eg: DZ47LE-32,Leakage circuit breaker

B. Rated Current; eg:25A

C. Pole and line number; eg: Single pole two line

D. Rated Voltage; eg:220V

E. Rated leakage circuit action current; eg:30mA

F. Quantity; eg:50pcs



1.Leakage circuit breaker rated connect breaking capacity

Shell Frame Rated Current

Pole

Neutral Line

Rated Current

Rated Short Circuit breaking capacity

Over-voltage Trip

Rated Voltage(V)

breaking capacity

COS

32

1

N

6.10

16.20

25.32

220

4000

0.7

C

2

 

2

N

380

3

 

3

N

4

 

32

1

N

6.10

16.20

25.32

220

4000

0.8

D

2

 

2

N

380

3

 

3

N

4

 

63

1

N

40.60

220

4000

0.8

C

2

 

2

N

380

3

 

3

N

4

 

2.Over-current protective feature

Item

Rated Current(A)

Starting Status

Test Current(A)

Test Time

Expected Results

Test Temperature

Remark

a

All

Cold

1.13In

t1h

Not trip

 

 

b

All

Hot

1.45In

t1h

Tripping

 

Up to rated current after 5s

c

32

Cold

2.55In

1st60s

Tripping

 

 

32

Cold

1st120s

d

All

Cold

5In(C)

10In(D)

t0.1h

Not trip

 

Closed auxiliary switch and connect power

e

All

Cold

10In(C)

14In(D)

t0.1s

Tripping

 

f

All

Cold

1.13In

t1h

Not trip

 

 

g

All

Hot

1.91In

t1h

Tripping

 

Up to rated current after 5s

h

All

Cold

1In

t1h

Not trip