ZMGY-2 High voltage reactive compensation controller

Print current page

Product Description

  • brief introduction
  • technical parameter
  • Product size

Application


ZMGY-2 high voltage reactive compensation controller is used for the reactive automatic compensating device at the circuit of 10kV and 6kV. It conducts the real-time monitoring and measuring with the power grid parameters like the reactive voltage, power factor.According to the change of reactive voltage, power factor or time, it fulfills the dynamic compensation for the high voltage circuit, plays an important role in improving the circuit power factor and voltage, reducing the wire loss, enhancing the quality of grid power grid, etc.


ZMGY-2 high voltage reactive compensation controller adopts the high-reliability microprocessor, with the functions of capacitor automatic switching control, capacitor protections against the over voltage, under voltage, harmonic wave.

Function characteristic


ZMGY-2 high voltage reactive compensation controller adopts the combination of inverse time lag and timing technology, controls the switching operation of capacitor through setting the capacitor capacity and reactive power calculation.


The inverse time lag technology can effectively guarantee the smoothness of capacitor operation, to avoid the electric appliance frequent switching operation or concussive switching operation due to fluctuation and abrupt change of voltage. In addition, to further prevent the capacitor frequent operation and concussive switching operation,the controller will give the estimation according to the capacity of capacitor, to guarantee the capacitor can't conduct the opposite operation after it operates if the system is in the abnormal area.


Main technical indicators


Working voltage AC100±20% Power consumption <5VA
Measuring voltage 110V  accuracy 0.5% Measuring current 0~5A  accuracy 1%
Control output 7A  AC220V Temperature -25℃~+65℃
Relative humidity <90% at 5℃ Air pressure 79.5kPa~106.0kPa
Installation Size 138*138mm Panel Size 144*144mm
Protection function  over-voltage 
under-voltage 
current harmonic




Installation Size


138×138mm