Print current page
Product Description
- brief introduction
- technical parameter
- Product size
Application
JKWF Series controller regards 8 single-chip microcomputer as core, adopts the control scheme of phase splitting sampling and compensation and common compensation and phase splitting compensated altogether, very suitable for reactive compensation with 50Hz, 0.4KV three-phase load imbalance power system.
Function characteristic
1.LED display the three-phase voltage, current, active power, reactive power, power, power, power factor and power network frequency, control parameter, etc..(With this controller can save ampere meter, voltmeter, universal change-over switch, etc in the cabinet.).
2.Strong anti-interference ability can resist 2000V interference pulse from power direct, and not crashing, does not lose the data, it is reliable to run steady.
3.Reactive power control physical quantity, high control precision;
4.The suer can revise the control parameter according to his own need, the control parameter is not lost to have a power failure.
5.With automatic discriminating phase function(sampling signal automatic be kept in the same state).
6.The input resistance of current sampling signal is smaller than 0.05Ω; it can be taken out from measuring loops directly.
7.With over-voltage, under-voltage, imperfect phase protective function.
8.Compensation mode:phase splitting compensation, phase splitting splitting compensation and three-phase compensation, the three-phase compensation.
9.Output mode:static state, dynamic state, compound etc.
10.Output loops 1-12 Loop
Technical data
Basic Parameter
Rated voltage: AC 220V±10%
Rated current: AC 0-5A Rated frequency:50Hz±5%
Control Parameter
Sensitivity: 100mA
COSφ Preset: 0.80-0.99; step length 0.01;
Factory preset 0.98 input and cutoff time delay: 2~250s, factory preset dynamic state 30s.
Over-voltage protection: 230-260V; step length 1V;
Factory prest 253V
CT variation: 50/5A-3000/5A; step length 1;
factory preset 500/5A
Capacitance capacity: 0-99kvar factory preset of each branch 10kvar
Contact capacity: dynamic state output of each branch DC12V×50mA
Static state output of each branch 380V×7A/200V×5A
Measuring accuracy
Voltage: ±0.5% Current: ±0.5% Power factor: ±1.0%
Active power: ±1.0%
Reactive power: ±1.0%
Installation Size
113*113mm