1.Full digital design, AC sampling, human machine interface is large LCD display.
2.Designed with friendly human care, module asse-mbly,flow-line figure
3.It can display power factor, voltage, current, active power, reactive power, distortion rate of total voltage harmonic waves, distortion rate of total current har-monic waves, frequency average value, and capacitor switching status and etc.
4.Parameter setting, to be instructed in Chinese words and English, digit input.
5.Capacitor control modes, two kinds: three-phase compensated together, combined compensation, you can set the control modes through the menu
6.Two working modes: Hand compensation/Auto Compensation
7.Parameter sampled is reactive power, it has the function of measuring harmonics and protections.
8.The controller provides RS-485, MODBUS standard communication port, used to connect with intelligent switchgear system.
Technical data
Ambient conditions:
Altitude:≤2500mm
Working temperature:-20℃~+60℃
Storing temperature:-40℃~+70℃
The working site shall have no corrosive gas, no con-ductive dust, no flammable or explosive medium, also nosevere vibration, and the snow, rain is not accessible.
Measurement data:
Measuring voltage:100V~290V
Measuring current: 0~6000A (primary) sensitivity: 50mA (secondary)
Measuring power factor: Lag 0.200 ~ Forward 0.200
Working source:220V±20%
Measuring frequency:47~53Hz
Display active power:0~6553Kw
Display reactive power:0~6553Kvar
Display the distortion rate of total voltage harmonics:0.0~100.0%
Display the distortion rate of total current harmonics:0.0~100.0%
Input / output signal:
Sampling voltage: L1, L2, L3 phase voltage
Sampling current: Bus phase current transformer secondary 0 ~ 5A
Control output:
Relay dry junction 5A / 250V Resistive (static)
12V 30mA / branch (dynamic)
RS485 network control
The compensation controller sampling voltage and sampling current must be the same, and the same name end.
Display performance:
LCD liquid crystal display data display refresh cycle ≤ 1s
Communication Interface Data:
Communication Interface: RS-485
Protocol: MODBUS communication protocol
Communication speed: 9600bps (no parity bit)
Measurement accuracy:
Voltage: ± 0.5% Active Power: ± 1.0%
Current: ± 0.5% Reactive power: ± 1.0%
Power factor: ± 1.0% Frequency: ± 0.1Hz
Setting data:
Total counters ratio: 50 ~ 9999 (/ 5)
Switch delay: 1-240s
Input threshold: 0.7 ~ -0.7
Cut-out threshold: 0.7 ~ -0.7 (cut-out threshold - investment threshold> 0.3)
Overvoltage settings: 220V ~ 260V
Undervoltage setting: 180V ~ 220V
Tension upper limit: 1% ~ 99% (99% to turn off this protection)
Fluffy ceiling: 1% ~ 99% (99% to turn off this protection)
Capacitor setting: Refer to the product specification for the capacitor setting procedure